| 2012-05-30 09:52:35 | BUILDING PLAN REVIEW |
| | PERMIT: 12050620 |
| | ADD: 529 S FLAGLER DR 31 H |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: (561)248-5266 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | APPLIED DATE: 5/21/2012 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: |
| | |
| | 1A) PROJECT DATA: INDICATES THE PLANS WERE DESIGNED TO |
| | THE 2007 EXISTING BUILDING CODE. MARCH 15/ 2012 |
| | STATWIDE THE 2010 FBC WAS ADOPTED BY SECTION 553.73 FS. |
| | |
| | 1B) PROJECT DATA INDICATES SUITE H TO BE 2091 SQ FT |
| | /200 = 10.45 OCCUPANTS, YOU ROUND UP TO 11 OCCUPANTS. |
| | BOAF INFORMAL INTERPRETATION 5479 12/18/2007. |
| | |
| | 1C) WIND LOAD CALCULATIONS ARE DESIGNED TO THE WRONG |
| | WIND CRITERIA, THE 2010 FBC-B WIND DESIGN IS ASCE 7-10, |
| | 2010 FBC-B 1609.1.1/ CHAPTER 35 REFRENECED STANDARDS. |
| | |
| | 1D) DETAIL A/ A-1 INDICATES THE USE OF WOOD PARTITIONS, |
| | PLEASE SEE THE REQUIRED USE OF 2010 FBC-B 603.1.1.1 |
| | FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN |
| | NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS LESS THAN 2 HOURS OR LESS. |
| | |
| | 2) ENGINEERING EXPRESS SITE SPECIFIC ENGINEERING FOR A |
| | CORNER MULLION, THERE APPEARS TO BE A DISCREPANCY |
| | BETWEEN THE FLOOR PLAN SHEET A-1 OF SET OF PLANS, WHICH |
| | IS ALSO INCORPORATED INTO THE ENGINEERING DOCUMENT |
| | INDEX SHEET A5 CLIENT SUPPLIED DOCUMENT AND THE MULLION |
| | CORNER DETAIL PAGE 4 OF 14 A 6'X6'X1/8 INCH ALUMINUM |
| | TUBE. |
| | THE TWO ARCHITECTURAL DETAILS INCORPARATE WHAT APPEARS |
| | TO BE A WALL SECTION BEFORE THE ATTACHMENT OF SLIDING |
| | GLASS DOORS. 2010 FBC-B 1715.5.5.2 LOAD TRANSFERS. |
| | MULLIONS SHALL BE DESIGNED TO TRANSFER THE DESIGN |
| | PRESSURE LOADS APPLIED BY THE WINDOW AND DOOR |
| | ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE. THE CODE |
| | LIMITS THE TRANSFER OF LOADING TO WINDOW & DOOR SYSTEMS |
| | TO MULLIONS. |
| | |
| | IF THIS 6"X6"X1/8 INCH ALUMINUM TUBE IS TO BE CONSIDERD |
| | A STRUCTURAL COLUMN WITH WALL SECTION DEPICTED THEN |
| | DETAIL THE INFILE AND TYPE OF FRAMING, ANCHORING, TYPE |
| | OF EXTERIOR WALL FINISH FOR THIS AREA. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, PART OF THE (MWFRS) |
| | MAIN WIND FORCE RESISTING SYSTEM. |
| | |
| | 3) PRODUCT APPROVALS PLEASE HIGHLIGHT (CIRCLE) TYPE OF |
| | GLAZINGFOR ASSOCIATED PRESSURES, IF STEEL REINFORCEMENT |
| | IS REQUIRED, ANCHORS FOR REVIEW BY THE DESIGN |
| | PROFESSIONAL. |
| | 2010 107.3.4.1*. THOSE PRODUCTS WHICH ARE REGULATED BY |
| | DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING |
| | BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4) ADDITIONAL INFORMATION REQUIRED, 107.2.1.3 SHEET A2 |
| | DEMO PLAN INDICATES THE REMOVAL OF A PORTION OF KITCHEN |
| | CABINETS AND EXISTING CONCRETE SLAB MAY BE EXPOSED, |
| | PLANS ARE SILENT IF NEW FLOOR COVERINGS ARE GOING TO |
| | TAKE PLACE UNDER THIS PERMIT. PLEASE BE AWARE OF 2010 |
| | FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | AND: |
| | 2010 603.1 ALLOWABLE MATERIALS. COMBUSTIBLE MATERIALS |
| | SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR TYPE II |
| | CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN |
| | ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3(2): |
| | 1. INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |
| | 2.INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| | SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |