| 2012-06-04 12:53:21 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. WIND SPEED TO BE A MINIMUM OF 169MPH, 160 SUBMITTED, | | | SEE FBC 1609.1.1. | | | | | | 2. EITHER REVISE EXPOSURE TO EXPOSURE D OR PROVIDE A | | | SIGNED, SEALED LETTER STATING RATIONALE FOR EXPOSURE C | | | DESIGN PRESSURES, FBC 1609.4. | | | | | | 3. WHEN RESUBMITTING, INCLUDE THE SHUTTER TO GLASS | | | SEPARATION, SEE SHEET 19 OF THE PRODUCT APPROVAL (6.25" | | | FOR WIND ZONE 4, SEE FBC 1609.1.2.4). | | | | | | 4. SHEET 19 LIMITS USE OF THIS PRODUCT TO -110PSF WHEN | | | WORKING WITH HV WINDOW BLADE, FBC 1609.1.1. | | | | | | | | | 3. |
|