2012-06-04 12:53:21****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. WIND SPEED TO BE A MINIMUM OF 169MPH, 160 SUBMITTED,
 SEE FBC 1609.1.1.
  
 2. EITHER REVISE EXPOSURE TO EXPOSURE D OR PROVIDE A
 SIGNED, SEALED LETTER STATING RATIONALE FOR EXPOSURE C
 DESIGN PRESSURES, FBC 1609.4.
  
 3. WHEN RESUBMITTING, INCLUDE THE SHUTTER TO GLASS
 SEPARATION, SEE SHEET 19 OF THE PRODUCT APPROVAL (6.25"
 FOR WIND ZONE 4, SEE FBC 1609.1.2.4).
  
 4. SHEET 19 LIMITS USE OF THIS PRODUCT TO -110PSF WHEN
 WORKING WITH HV WINDOW BLADE, FBC 1609.1.1.
  
  
 3.