2012-06-11 15:03:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE INFORMATION (SUCH AS A PRINTED MAP) WHICH
 SHOWS THAT FBC 1609.1.1 EXCEPTION 5 ALLOWS DESIGN TO
 130MPH. PLEASE NOTE THAT THE ASCE7-05 AND 7-02 MAPS HAD
 WPB IN THE 140MPH WIND ZONE, SEE GENERAL NOTE 1B.
  
 2. PLEASE SEE FBC 1609.8 AND REVISE DESIGN CRITERIA TO
 INCLUDE THIS REQUIREMENT.
  
  
  