| 2012-06-25 10:19:48 | BUILDING PLAN REVIEW |
| | PERMIT: 12050570 |
| | ADD: 222 LAKEVIEW AVE # 148 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: (954)270-1894 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1: |
| | |
| | 1A)2ND REQUEST, PLEASE PROVIDE THE USAGE FOR THE |
| | BUSINESS OCCUPANCY FOR ROOM 148 & 150? IT APPEARS THAT |
| | ROOM 148 IS TO BE OCCUPIED BUT BOTH SUITES INDICATE |
| | THEY ARE UNOCCUPIED SPACE? 106.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. THE RESPONCE INDICATES BOTH |
| | ROOMS ARE UNOCCIPIED AND WILL NOT HOUSE ANY PEOPLE BUT |
| | THE RESPONCE TO COMMENT (1D) INDICATES AN AUTOMATIC |
| | DOOR OPENER FOR ADA ACCESS WILL BE INSTALLED, THIS |
| | APPEARS THAT THERE WILL BE AN OCCUPANT LOAD AND WILL BE |
| | OCCUPIED. THE SPACE # 148 THE RESPONCE INDICATES THIS |
| | AREA TO BE USED AS A FURNITURE SHOWROOM. 2010 FBC-B |
| | 309.1 INDICATES THE OCCUPANCY TYPE TO BE A MERCANTILE |
| | "FOR THE DISPLAY AND SALE OF |
| | MERCHANDISE AND INVOLVES STOCKS OF GOODS AND SALE OF |
| | MERCHANDISE INCIDENTIAL TO SUCH PURPOSES AND ACCESSIBLE |
| | TO THE PUBLIC. PLEASE CORRECT THE COVER SHEET AND |
| | ASSOCIATED OCCUPANT LOAD. |
| | |
| | 1B) 2ND REQUEST, CEILING NOTE # 2 AND FLOOR PLAN NOTE # |
| | 8 INDICATE THE USE OF NEW STRETCHED FABRIC SAIL CABLE |
| | MOUNTED TO CEILING DECK ABOVE. SEE DETAIL FB-3 ON SHEET |
| | A3.1 FOR SPEC. |
| | MISSING DETAIL ON SHEET A3.1. PLEASE PROVIDE MOUNTING |
| | DETAIL AND PRODUCT COMPLIANCE FOR 2010 FBC-B 803.1.4 |
| | ACCEPTANCE CRITERIA FOR TEXTILE WALL OR CEILING |
| | COVERINGS TO ASTM 84 OR UL723. |
| | SUBMITTED PRODUCT SPEC JUXTAFORM HAS TWO TYPES OF |
| | FABRIC : |
| | STANDARD FABRIC SPECIFICATIONS WITH ASTM E84 |
| | MESH FABRIC SPECIFICATIONS NO ASTM E 84 TESTING |
| | WHICH OF THE FABRICS ARE GOING TO BE INSTALLED? |
| | |
| | 1C) 2ND REQUEST, PLANS ARE NOT CLEAR AS TO SUITE # 150 |
| | THE UNOCCUPIED SPACE, IS THIS PART OF THE SAME |
| | TENANTCY, OR IS THE WALL SEPERATING THE TWO ROOMS A |
| | TENANT SEPERATION WALL THAT WOULD REQUIRE FIRE RATING |
| | PER 2010 FBC-B SECTION # 709.1(6). IS THE AREA |
| | UNOCCUPIED AREA # 150 UNDER THIS TENANCY? IF THE AREA # |
| | 150 IS NOT UNDER THE SAME TENANCY THEN IT IS CONSIDERED |
| | A TENANT SPERATION WALL 2010 FBC-B. IF THIS SPACE IS TO |
| | BE CONSIDERED A SEPERATE TENDANCY A SHELL SPACE A 1 |
| | HOUR TENANT SEPERATION WALL WILL BE REQUIRED. |
| | |
| | 1D) COMPLIED. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |