| Date |
Text |
| 2012-06-07 16:22:03 | BUILDING PLAN REVIEW |
| | PERMIT: 12050570 |
| | ADD: 222 LAKEVIEW AVE # 148 |
| | CONT: HOLT LEE CONSTRUCTION |
| | TEL: (954)270-1894 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1.1: |
| | |
| | 1A) PLEASE PROVIDE THE USAGE FOR THE BUSINESS OCCUPANCY |
| | FOR ROOM 148 & 150? IT APPEARS THAT ROOM IS TO BE |
| | OCCUPIED BUT BOTH SUITES INDICATE THEY ARE UNOCCUPIED |
| | SPACE? 106.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1B) CEILING NOTE # 2 AND FLOOR PLAN NOTE # 8 INDICATE |
| | THE USE OF NEW STRETCHED FABRIC SAIL CABLE MOUNTED TO |
| | CEILING DECK ABOVE. SEE DETAIL FB-3 ON SHEET A3.1 FOR |
| | SPEC. |
| | MISSING DETAIL ON SHEET A3.1. PLEASE PROVIDE MOUNTING |
| | DETAIL AND PRODUCT COMPLIANCE FOR 2010 FBC-B 803.1.4 |
| | ACCEPTANCE CRITERIA FOR TEXTILE WALL OR CEILING |
| | COVERINGS TO ASTM 84 OR UL723. |
| | |
| | 1C) PLANS ARE NOT CLEAR AS TO SUITE # 150 THE |
| | UNOCCUPIED SPACE, IS THIS PART OF THE SAME TENANTCY, OR |
| | IS THE WALL SEPERATING THE TWO ROOMS A TENANT |
| | SEPERATION WALL THAT WOULD REQUIRE FIRE RATING PER 2010 |
| | FBC-B SECTION # 709.1(6). |
| | |
| | 1D) THE FLOOR PLAN NOTE # 10 INDICATES AUTOMATIC DOOR |
| | OPENERS, ARE THESE ELECTRIC ACCESS CONTROLED DOORS, |
| | (TOUCH PADS) PLEASE PROVIDE ADDITIONAL INFORMATTION |
| | INDICATING COMPLIANCE WITH FBC-B 1008.1.4.2 FOR |
| | POWER-OPERATED DOORS AND 1008.1.4.4 FOR |
| | ACCESS-CONTROLLED EGRESS DOORS. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |