2012-07-27 13:03:52BUILDING PROVISO:
 SHEET A-2 NOTE 20 INDICATES A NEW SHOWER CEILING M.R.
 G.W.B. THE PLANS DO NOT INDICATE THE THICKNESS OF THE
 MOISTURE RESISTANT BYPSUM WALL BOARD NOR DO THEY
 INDICATE THE FRAMING SPACING. 2509.3. ON CEILINGS WHERE
 FRAME SPACING EXCEEDS 12 INCHES (305 MM) O.C. FOR
 1/2-INCH-THICK (12.7 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR
 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING
 BOARD.
  