Date Text
2012-05-22 08:57:24MAXIMUM OVERCURRENT PROTECTION FOR 3/0 ALUMINUM FEEDERS
 IS 155 AMPS. NEC T. 310.16
 NON METALLIC SHEATHED CABLE (SEE PLAN NOTE 5) IS NOT
 ACCEPTABLE FOR TYPE I AND TYPE II CONSTRUCTION. NEC
 334.12
 JACUZZI/ HOT TUB REQUIRE GFCI PROTECTION. NEC 680.43(A)
 LIGHTING OUTLETS ABOVE HOT TUB MUST BE GFCI PROTECTED
 AND SUITABLE FOR DAMP LOCATIONS. NEC 680.43 (B)
 ADD GFCI PROTECTED KITCHEN COUNTER TOP RECEPTACLES AT
 THE SPACES SEPARATED BY APPLIANCES AND SINKS AND SO
 THAT NO POINT ALONG THE COUNTER IS MORE THAN 24 INCHES
 FROM A RECEPTACLE. NEC 210.52 (C)
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER