| Plan Review Notes For Permit 12050524 |
| Permit Number |
12050524 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-22 08:57:24 | MAXIMUM OVERCURRENT PROTECTION FOR 3/0 ALUMINUM FEEDERS | | | IS 155 AMPS. NEC T. 310.16 | | | NON METALLIC SHEATHED CABLE (SEE PLAN NOTE 5) IS NOT | | | ACCEPTABLE FOR TYPE I AND TYPE II CONSTRUCTION. NEC | | | 334.12 | | | JACUZZI/ HOT TUB REQUIRE GFCI PROTECTION. NEC 680.43(A) | | | LIGHTING OUTLETS ABOVE HOT TUB MUST BE GFCI PROTECTED | | | AND SUITABLE FOR DAMP LOCATIONS. NEC 680.43 (B) | | | ADD GFCI PROTECTED KITCHEN COUNTER TOP RECEPTACLES AT | | | THE SPACES SEPARATED BY APPLIANCES AND SINKS AND SO | | | THAT NO POINT ALONG THE COUNTER IS MORE THAN 24 INCHES | | | FROM A RECEPTACLE. NEC 210.52 (C) | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|