| 2012-06-04 12:31:36 | BUILDING PLAN REVIEW |
| | PERMIT: |
| | ADD: |
| | CONT: |
| | TEL: (561)###-#### |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEWREVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-2: |
| | |
| | 1A) NOTE #16 INDICATES THE USE OF NEW ENGINEERED WOOD |
| | WITH CORK UNDER LAYMENT. PLEASE PROVIDE COMPLIANCE FOR: |
| | 1A)(1) 2010 FBC-B 603.1.2 (2) INSULATION INSTALLED |
| | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE |
| | THAN 200. |
| | |
| | 1B) (2) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2) SHEET A-2 NOTE 20 INDICATES A NEW SHOWER CEILING |
| | M.R. G.W.B. THE PLANS DO NOT INDICATE THE THICKNESS OF |
| | THE MOISTURE RESISTANT BYPSUM WALL BOARD NOR DO THEY |
| | INDICATE THE FRAMING SPACING. 2509.3. ON CEILINGS WHERE |
| | FRAME SPACING EXCEEDS 12 INCHES (305 MM) O.C. FOR |
| | 1/2-INCH-THICK (12.7 MM) WATER-RESISTANT GYPSUM BACKING |
| | BOARD AND MORE THAN 16 INCHES (406 MM) O.C. FOR |
| | 5/8-INCH-THICK (15.9 MM) WATER-RESISTANT GYPSUM BACKING |
| | BOARD. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | 6/06/12 E-MAILS FROM DESIGNER KERMIT WHITE PROVIDING |
| | DOCUMENTS FOR |
| | FLAME SPREAD & SMOKE DEVELOPMENT AND COMPLIANCE WITH |
| | 1207.3 STRUCTURE BORN SOUNDINSULATION. OK, APPROVED FOR |
| | THESE COMPONENTS. JW |
| | |
| | |
| | |
| | |