Plan Review Notes
Plan Review Notes For Permit 12050519
Permit Number 12050519
Review Stop M
Sequence Number 1
Notes
Date Text
2012-06-26 16:58:25REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M201, PROVIDE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS TO SHOW THE PROPOSED EXHAUST INSTALLATION
 IS IN COMPLIANCE WITH THE DRYER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. AT THIS TIME, THE PROPOSED
 BOOSTER FANS ARE NOT ACCEPTABLE FOR THIS APPLCATION.
 SEE FBC-M 507.1.
  
 2. PAGE M204, PROVIDE DETAIL FOR ATTACHMENT OF NEW
 ADAPTOR TO EXISTING CURB AND ATTACHMENT OF AHU TO THE
 ADAPTOR. INCLODE SIZE, TYPE, NUMBER, MATARIAL AND
 SPACING OF FASTENERS. THIS REQUIREMENT ALSO APPLIES TO
 ALL CONDENSERS AND FANS INSTALLED OUTDOORS. SEE FBC-M
 301.12
  
 3. PROVIDE COOLING AND HEATING OAD CALCULATIONS FOR ALL
 EXUIPMENT BEING NEWLY INSTALLED OR REPLACED PER FBC-EC
 SECTION 104.6.1.
  