2012-05-31 14:07:034847 FRED GLADSTONE DRIVE
 PERMIT #12050519
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. "NO SMOKING" SIGNS SHALL
 BE PLACE THROUGHOUT THE CONSTRUCTION AND DEMOLITION
 AREAS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET A601: NEW FIRE-RATED STAIR DOORS SHALL HAVE A
 MINIMUM FIRE-RESISTANCE OF 1-HOUR.
  
 SHEETS FP201, FP202 & FP203: SPRINKLER ZONES DO NOT
 MATCH SMOKE COMPARTMENTS. CURRENTLY THREE DIFFERENT
 FLOW SWITCHES ALL SERVE PART OF THE SAME SMOKE
 COMPARTMENT. LOCATION OF THE SPRINKLER ALARM ACTIVATION
 AND THE ABILITY TO CONVEY THE INFORMATION TO THE STAFF
 ARE CRITICAL TO A SUCCESSFULLY COORDINATED SMOKE ZONE
 FIRE RESPONSE.
  
 SHEET E502: NO FIRE ALARM NOTIFICATION APPLIANCE
 LOCATED IN PRIVATE DINING #247 OR ACTIVITY ROOM #256.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW