| 2012-05-31 14:07:03 | 4847 FRED GLADSTONE DRIVE |
| | PERMIT #12050519 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. "NO SMOKING" SIGNS SHALL |
| | BE PLACE THROUGHOUT THE CONSTRUCTION AND DEMOLITION |
| | AREAS. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | SHEET A601: NEW FIRE-RATED STAIR DOORS SHALL HAVE A |
| | MINIMUM FIRE-RESISTANCE OF 1-HOUR. |
| | |
| | SHEETS FP201, FP202 & FP203: SPRINKLER ZONES DO NOT |
| | MATCH SMOKE COMPARTMENTS. CURRENTLY THREE DIFFERENT |
| | FLOW SWITCHES ALL SERVE PART OF THE SAME SMOKE |
| | COMPARTMENT. LOCATION OF THE SPRINKLER ALARM ACTIVATION |
| | AND THE ABILITY TO CONVEY THE INFORMATION TO THE STAFF |
| | ARE CRITICAL TO A SUCCESSFULLY COORDINATED SMOKE ZONE |
| | FIRE RESPONSE. |
| | |
| | SHEET E502: NO FIRE ALARM NOTIFICATION APPLIANCE |
| | LOCATED IN PRIVATE DINING #247 OR ACTIVITY ROOM #256. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |