2012-07-05 15:28:33BUILDING PLAN REVIEW
 PERMIT: 12050519
 ADD: 4847 FRED GLADSTONE DR
 CONT: THE WHITING TURNER CO.
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-2E CODES AND STANDARDS INDICATES THE WIND
 DESIGN CRITERIA TO BE ASCE 7-10 BLDG CAT LLL ON THE
 SAME SHEET THE WIND DESIGN CRITERIA INDICATES UNDER THE
 HEADING ALLOWABLE (NOMINAL) WIND DESIGN LOAD SCHEDULE
 INDICATES THE 2007 FBC NOT THE 2010 FBC. THE PRESSURES
 SHOULD REFLECT THE 2010 FBC, EXPOSURE C AND HEIGHT
 ADJUSTMENT FACTORS.
  
 2) 2010 WPB ADMINISTRATIVE CODE CHAPTER 1 FBC 107.3.4.1
 THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE
 CHARGE SHALL BE RESPONSIBLE FOR REVIEWING AND
 COORDINATING
 SUBMITTAL DOCUMENTS PREPARED BY OTHERS, INCLUDING
 PHASED AND DEFERRED SUBMITTAL ITEMS, FOR COMPATIBILITY
 WITH THE DESIGN OF THE BUILDING. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)
 (B) WINDOWS
 (E) SHUTTERS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 4) 2010 FBC-B 420.4.2.5 EXTERIOR UNIT STANDARDS.
 420.4.2.5.1 ALL EXTERIOR WINDOW UNITS, SKYLIGHTS,
 EXTERIOR LOUVERS AND EXTERIOR DOOR UNITS INCLUDING
 VISION PANELS AND THEIR ANCHORING SYSTEMS SHALL BE
 IMPACT RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF THE TESTING
 APPLICATION STANDARDS (TAS) 201, 202, AND 203 OF THIS
 CODE IN ACCORDANCE WITH THE REQUIREMENTS OF SECTIONS
 1626.2 THRU 1626.4 OF THIS CODE. THE IMPACT RESISTANT
 COVERINGS MAY BE EITHER PERMANENTLY ATTACHED OR MAY BE
 REMOVABLE IF STORED ON SITE OF THE FACILITY.
 420.4.2.5.2 THE LOCATION OR APPLICATION OF EXTERIOR
 IMPACT PROTECTIVE SYSTEMS SHALL NOT PREVENT REQUIRED
 EXIT EGRESS FROM THE BUILDING.
 420.4.2.5.3 WHEN NOT BEING USED TO PROTECT THE WINDOWS,
 THE PERMANENTLY ATTACHED IMPACT RESISTANT COVERINGS
 SHALL NOT REDUCE THE PERCENTAGE OF THE CLEAR WINDOW
 OPENING BELOW THAT REQUIRED BY THIS CODE FOR THE
 PATIENT ROOM.
  
 5) MECHANICAL SHEET E-M204 DETAIL # 1 THE PLANS DO NOT
 INDICATE WHAT MATERIALS THE NEW CURB EXTENSION WILL BE
 MADE FROM NOR THE ATTACHMENT TO THE EXISTING CURB NOR
 THE
 MECHANICAL EQUIPMENT ABOVE. MECHANICAL SHEET E-M301
 ROOF EXHAUST FAN DETAIL PLEASE SEE NOTE ALL ROOF
 MOUNTED EQUIPMENT MUST ADHERE TO THE CURRENT HURRICANE
 CODES REGARDING TIE DOWN & WIND RESISTANCE.
  
 6) PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN
 CONRAD AT (561) 805-6666TO SEE IF WELDING CERTIFICATES
 WOULD BE REQUIRED OR IF A RESIDENT INSPECTOR WOULD BE
 REQUIRED
 FOR ALL INTERIOR STRUCTURAL WORK INCLUDING SHORING AND
 OR RESHORING.
  
 7) SHEET S-1E IT APPEARS THE NEW W12X30 IS MISSING A
 ATTACHMENT DETAIL TO THE NEW W16X50? ADDITIONAL
 INFORMATION IS REQUIED.
 107.2.1 WPB ADMINISTRATIVE CODE INFORMATION ON
 CONSTRUCTION DOCUMENTS. SEE PROJECT DOCS FOR LOCATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  