| Plan Review Notes For Permit 12050518 |
| Permit Number |
12050518 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-25 11:36:29 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2010 CODE FAMILY | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | AS OF MARCH 15, 2012, THE FLORIDA BUILDING CODE, ENERGY | | | VOLUME REQUIRES COOLING AND HEATING LOAD CALCULATIONS | | | FOR MECHANICAL EQUIPMENT REPLACEMENT IN EXISTING | | | BUILDINGS. | | | PROVIDE COOLING AND HEATING LOAD CALCULATIONS TO VERIFY | | | EQUIPMENT SIZING IS IN COMPLIANCE WITH THE REQUIREMENTS | | | OF THE CODE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|