2012-05-30 16:53:36BUILDING PLAN REVIEW
 PERMIT: 12050518
 ADD: 4847 FRED GLADSTONE RESNICK PAVILION
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800 CONTACT HENRY SHAWAH
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET S-1R:
  
 1A) CODES AND STANDARDS WIND LOADS AS PER ASCE 7-10
 MISSING THE HEIGHT ADJUSTMENT FACTORS 2010 FBC-B TABLE
 1609.7(2). THIS MAY EFFECT WIND LOAD TABLE FOR ROOFS
 AND WALL WIND LOADS.
  
 1B) NOTE 2A INDICATES THE PLANS WERE DESIGNED TO FBC
 2007/09. AS OF MARCH 15/ 2012 THE STATE OF FLORIDA
 ADOPTED THE 2010 FBC PER FS 533.73.
  
 2) SHEET R-A621 INDICATES THE WINDOW SIZES BUT NO
 PRODUCT APPROVALS WERE SUBMITTED INDICATING COMPLIANCE
 WITH THE 2010 EXISTING BUILDING CODE SECTION 606.4
 REPLACEMENT OF WINDOWS. REPLACEMENT OF WINDOWS AND
 DOORS. THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, OPERATIVE AND INOPERATIVE WINDOWS SHALL BE
 DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 OF
 THE FLORIDA BUILDING CODE, BUILDING . 1609.1.2
 PROTECTION OF OPENINGS &1609. 6.4.4.1 COMPONENTS &
 CLADDING,
  
 3) 2010 FBC 107.3.4.1* THOSE PRODUCTS THAT ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 THE SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 EXISTING BUILDING CODE LEVEL II SECTION 711.1
 ALTERATIONS SUBJECT TO THIS SHAPTER SHALL COMPLY WITH
 THE REQUIREMENTS OF THE FL BLDG CODE ENERGY
 CONSERVATION. 2010 ENERGY CODE 101.4.1 EXISTING
 BUILDINGSSHALL MEEET THE CRITERIA IN TABLE 101.4.1
 (ENERGY). RENOVATIONS FOOTNOTE "D" IS GOING TO BE THE
 TRIGGERING FACTOR SEE DEFINITIONS FOR RENOVATION AND IS
 THE RENOVATION 30% OR MORE WITHIN A YEAR PERIOD, IS
 THIS 30% OF THE ASSESSED VALUE OF THE BUILDING? IF SO
 THEN THE REQUIREMENTS OF 503, 504, 505 WOULD APPLY.
  
 5) SHEET R-A101 & R-A103 INDICATE SEMI-PRIVATE ROOMS
 ARE BEING CONVERTED TO PRIVATE ROOMS THE PLANS DO NOT
 INDICATE COMPLIANCE WITH 420.3.3 RESIDENT ROOMS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  