| Plan Review Notes For Permit 12050508 |
| Permit Number |
12050508 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-21 12:50:53 | RESIDENTIAL (R2) SHUTTERS BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- ACCORDION SHUTTERS NOA 07-0402.06 SUBMITTED EXPIRED | | | ON APRIL 13, 2012. NEED TO PROVIDE CURRENT NOA AS | | | REQUIRED BY DCA RULE 9N-3. PROVIDE 2 COPIES. | | | | | | 2- PROVIDE COMPLETE INFORMATION ON THE STORMS SHUTTERS | | | INSTALLATION SCHEDULE AS REQUIRED BY SEC. 107.2.1.3 OF | | | CITY AMENDMENTS TO FBC. | | | A) SPECIFY THE SHUTTER GLASS SEPARATION. SEE PRODUCT | | | APPROVAL FOR REQUIRED SEPARATION. | | | B) SPECIFY SPECIFIC ANCHOR TO BE USED. SEE PRODUCT | | | APPROVAL. NEED TO VERIFY ANCHOR SPACING. | | | C) CLEARLY IDENTIFY WHICH WALL MOUNTING DETAIL IS GOING | | | TO BE USED. ACCORDION SHUTTERS DRAWINGS SUBMITTED SHOW | | | 5 DIFFERENT WALL MOUNTING DETAILS. | | | D) CLARIFY HOW OBTAINING 3" MINIMUM EDGE DISTANCE IF | | | THE SHUTTERS SPAN IS THE SAME AS THE OPENING HEIGHT TO | | | BE PROTECTED. IT LOOKS LIKE THE MINIMUM EDGE DISTANCE | | | IS NOT ACHIEVABLE CONSIDERING THE SIZE OF THE WALL | | | HEADERS AND THE FACT THAT THE EDGE DISTANCE EXCLUDES | | | THE STUCCO THICKNESS. | | | | | | 3- PROVIDE CLEAR AND LEGIBLE ACCORDION SHUTTERS | | | DRAWINGS. DRAWINGS SUBMITTED ARE INCOMPLETE. DRAWINGS | | | ARE CUT IN PIECES AND ARE NOT LEGIBLE. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|