| Plan Review Notes For Permit 12050406 |
| Permit Number |
12050406 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-29 10:45:02 | PLANS DENIED | | | | | | 1. REVISE PLAN TO INCLUDE DUCT SIZE OF THE RIGID DUCT | | | TRUNK LINE FROM AHU, FBC 2010 107.3.5.3. | | | | | | 2. REVISE PLAN TO SHOW BALANCED RETURN AIR, FBC 2010 | | | RESIDENTIAL M 1602.4. | | | | | | 3. REVISE PLAN TO SHOW LOCATION AND SIZE OF RETURN AIR, | | | FBC 2010 107.3.5.3. | | | | | | 4. TWO SETS OF THE PRODUCT APPROVAL ARE REQUIRED, FBC | | | 107.1. PLEASE MARK OPTION OF ATTACHMENT PROPOSED TO | | | SHOW COMPLIANCE WITH FBC RESIDENTIAL M 1307.2.1. | | | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | | 561-805-6732 | | | | | | |
|