| Plan Review Notes For Permit 12050398 |
| Permit Number |
12050398 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-06-29 14:40:09 | 6/28/2012 PLANS REVIEWED BY FIRE ***DENIED*** | | | PERMIT #12050398 | | | | | | 1. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE | | | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA | | | EDITION OF NFPA 1 AND NFPA 101. | | | 2. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | 3. PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY | | | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, | | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | | TRAVEL ETC. | | | 4. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | | | | DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | OFFICE OF THE FIRE MARSHAL | | | (561) 805-6722 | | | | | | | | | |
|