| 2012-05-30 12:51:43 | 12050398 | | | 477 S. ROSEMARY AVE #320-328 | | | | | | VERIFY THE WORKING CLEARANCES IN THE ELECTRICAL | | | EQUIPMENT ROOMS ARE ADEQUATE FOR THE NEW EQUIPMENT. NEC | | | 110.26 | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | NEW SERVICE, SWITCH GEAR AND ELECTRIC PANELS. NEC | | | 110.9, 110.10 | | | | | | PLANS ARE UNCLEAR AS TO WIRING METHODS PROPOSED WITHIN | | | THE IT ROOM - 320B. IS IT INTENDED THAT THIS ROOM BE | | | TREATED AS AN INFORMATION TECHNOLOGY EQUIPMENT ROOM | | | WITH A DISCONNECTING MEANS, RAISED FLOORS AND RATED | | | WALLS? NEC ARTICLE 645 | | | | | | VERIFY THE ILLUMINATION AND BRIGHTNESS IN THE | | | CLASSROOMS MEETS ENERGY CODE REQUIREMENTS. FBC 443.3.7 | | | | | | PROVIDE A SEPARATE PERMIT AND PLANS FOR THE IT ROOM | | | FIRE SUPPRESSION SYSTEM | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|