| Plan Review Notes For Permit 12050341 |
| Permit Number |
12050341 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-09-24 11:26:44 | 12050341 | | | 1711 LONGWOOD ROAD | | | NEW ELECTRIC SYSTEM | | | | | | SERVICE CONDUCTORS MAY NOT BE MIXED WITHIN THE SAME | | | SERVICE RACEWAY (JUNCTION BOX) AS OTHER CONDUCTORS. NEC | | | 230.7 | | | | | | PANEL BOARD ?PM2? REQUIRES A LARGER FEEDER. PARALLEL | | | CONDUCTORS ARE LIMITED TO 1/0 AND LARGER. NEC T. | | | 310.16, 310.4 | | | | | | PROVIDE GROUNDING AND BONDING SCHEMATIC FOR THE | | | SEPARATELY DERIVED SYSTEMS. NEC 250.30 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|