Plan Review Notes
Plan Review Notes For Permit 12050341
Permit Number 12050341
Review Stop P
Sequence Number 1
Notes
Date Text
2012-05-15 09:23:09FBC 2010 PLUMBING
 FBC 2010 ACCESSIBILITY
 REVIEW #1
 DENIED:
  
 1. THE NEW MENS ROOM #120 DEOE NOT HAVE A STALL
 COMPLYING WITH FBC 2010 ACCESSIBILITY 213.3.1 TOILET
 COMPARTMENTS AND 604.8.1. SEE FIGURE 604.8.1.6
  
 2. ONE URINAL WILL BE REQUIRED TO BE MOUNTED AT A MAX.
 OF 17" AFF TO RIM.- 213.3.3
  
 3. THE CENTER OF THE HC LAV ON SHEET A-8 WILL BE 1'-3"
 IF THE STALL IS THE MIN. 7'-1"
  
 4. A HI/LO DRINKING FOUNTAIN IS LISTED ON P-1 BUT NOT
 FOUND ON THE PLUMBING DRAWING.
  
 5. HOT WATER IS REQUIRED AT THE SERVICE SINK AND
 KITCHEN SINK. FBC 2010 PLUMBING 607.1
  
 6. A VENT IS REQUIRED FOR THE GRINDER PUMP PER
 MANUFACTURERS INSTRUCTIONS.
  
 7. THE KITCHEN SINK AND SERVICE SINK ARE SHOWN
 CONNECTING TO A WET VENT. FIXTURES OTHER THAN BATHROOM
 FIXTURES ARE REQUIRED TO CONNECT DOWNSTREAM OF THE WET
 VENT SYSTEM.
 FBC 2010 PLUMBING 909.1
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  