| Plan Review Notes For Permit 12050341 |
| Permit Number |
12050341 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-09-20 16:54:20 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2010 | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. NO VENTIALTION INFORMATION PROVIDED. PROVIDE | | | VENTILATION CALCULATIONS FOR ALL NEWLY CONSTRUCTED OR | | | RECONFIGURED SPACES AS WELL AS ANY SPACES WHICH | | | CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M SECTION 403. | | | | | | 2. IT IS NOT POSSIBLE TO DETERMINE WHICH DUCTWORK IS | | | NEW AND WHICH DUCTWORK IS EXISTING TO REMAIL. PLEASE | | | INDICATE ON PLANS WHICH DUCTWORK WILL BE NEWLY | | | INSTALLED AS PART OF THE SCOPE OF THIS WORK PER FBC-B | | | 106.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|