Plan Review Notes
Plan Review Notes For Permit 12050341
Permit Number 12050341
Review Stop M
Sequence Number 1
Notes
Date Text
2012-09-20 16:54:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NO VENTIALTION INFORMATION PROVIDED. PROVIDE
 VENTILATION CALCULATIONS FOR ALL NEWLY CONSTRUCTED OR
 RECONFIGURED SPACES AS WELL AS ANY SPACES WHICH
 CONSTITUTE A CHANGE OF OCCUPANCY PER FBC-M SECTION 403.
  
 2. IT IS NOT POSSIBLE TO DETERMINE WHICH DUCTWORK IS
 NEW AND WHICH DUCTWORK IS EXISTING TO REMAIL. PLEASE
 INDICATE ON PLANS WHICH DUCTWORK WILL BE NEWLY
 INSTALLED AS PART OF THE SCOPE OF THIS WORK PER FBC-B
 106.1.
  