2012-05-15 11:46:0012050341
 1711 LONGWOOD RD.
 ELECTRIC ADDITION
  
 PLEASE CLARIFY THE SCOPE OF THE ELECTRIC WORK PROPOSED.
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY
 THE ELECTRICAL RISER PLAN TO SHOW ALL METERS,
 GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE
 BUILDING ACCURATELY LABELED.
 NEC 230.2, 230.71, 230.72
 INDICATE THE SIZE OF THE OVERCURRENT PROTECTION FOR THE
 FEEDERS FROM THE TRANSFORMER TO THE JUNCTION BOX.
 INDICATE THE SIZE AND LOCATION OF OVERCURRENT
 PROTECTION PROPOSED FOR THE NEW PANEL BOARDS. PROVIDE
 PANEL BOARD SCHEDULES AND LABELS FOR TRANSFORMERS AND
 PANELS WHICH MATCH THE RISER PLAN. NEC 215.5
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC505.1, 505.2
 VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED
 WORKING SPACE HAS BEEN PROVIDED FOR THE ELECTRICAL
 EQUIPMENT AND PANEL BOARDS. NEC 110.26, 240.24, 408.17
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  