| 2012-05-31 09:31:11 | BUILDING PLAN REVIEW |
| | PERMIT:12050341 |
| | ADD: 1711 LONGWOOD RD |
| | CONT: MIKE T LANG |
| | TEL: (561)262-0915 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET INDICATES THIS PROJECT WITH THE MAIN |
| | OCCUPANCY TYPE BEING A F1 OCCUPANCCY. TO DETERMINE IF |
| | THIS IS A F1 OR A F2 OCCUPANCY A DESCRIPTION OF THE |
| | PROCESS THAT IS TO TAKE PLACE WOULD BE HELPFULL, PLANS |
| | INDICATE TTHE USE OF A MACHINE SHOP WHICH WORKS WITH |
| | METALS, SECTION 306.3 OF THE FBC-B INDICATES THAT METAL |
| | PRODUCTS THE FABRICATION & ASSEMBLY OF METAL PRODUCTS. |
| | |
| | 2) IF THIS PLAN IS TO BE CONSIDERED A F2 OCCUPANCY THEN |
| | THEN THIS REVIEW WILL NEED TO CONSIDER THIS A MIXED USE |
| | BUILDING SINCE THE ACCESSORY OCCUPANCIES COVERS OVER |
| | 10% OF THE BUILDING (FLOOR) AREA. THE DESIGNER WILL |
| | NEED TO CONSIDER SEPERATED OR NON-SEPERATED |
| | OCCUPANCIES, SEE 508.3 & 508.4 ANAD TABLE 508.4 FOR |
| | RATING OF OCCUPANCY SEPERATION WALLS. |
| | |
| | 3) IF THE DESIGNER OF RECORD DECIDES TO HAVE SEPERATED |
| | OCCUPANCIES WITH ASSOCIATED RATED WALLS THEN OPENING |
| | PROTECTIVES WILL NEED TO BE CONSIDERED FOR DOOR |
| | OPENINGS WITHIN THE WALL PER TABLE 715.4. |
| | |
| | 4) THE MANUFACTURING PROCESS OF FACTORY PROCESS IS |
| | UNKNOWN AT THIS TIME, A LIST OF MATERIALS THAT WILL BE |
| | USED IN THE MANUFACTURING PROCESS AND MSDS SHEETS WILL |
| | BE REQUIRED BEFORE A THROROUGH REVIEW CAN TAKE PLACE. |
| | PLEASE NOT THAT THE MACHINE SHOPS MAY BE CONSIDERED A |
| | HAZARDOUS OCCUPANCY OR POSSIBLY JUST CONTROLED AREAS |
| | DEPENDING ON THE AMOUNT OF FIRE OR EXPLOSIVE HAZARD IS |
| | ASSOCIATED WITH PROCESSING. PLEASE REVIEW COMBUSTIBLE/ |
| | FLAMMABLE DUST , (ALUMINUM FILINGS) TABLE 414 FOOTNOTES |
| | A & C. |
| | |
| | 5) MACHINE SHOP 2 & 3 BOTH HAVE PROBLEMS WITH EXITING, |
| | THE PLANS SHOW EXITING THROUGH WHAT APPEARS TO BE A |
| | OVERHEAD DOOR. PLEASE REVIEW FBC-B 1008.1.2 DOORS MUST |
| | BE SIDE SWINGING. |
| | |
| | 6) SHEET A-6 INDICATES WHAT APPEARS TO BE TWO MEZZANINE |
| | AREAS: |
| | |
| | 6A) THE PLANS INDICATE THIS BUILDING TO BE A TYPE IIA |
| | PLEASE REVIEW FBC-B 603.1.1 FIRE RETARDENT TREATED WOOD |
| | WILL BE REQUIRED. |
| | |
| | 6B) 110.4.2 STORAGE & FACTORY- INDUSTRIAL OCCUPANCIES. |
| | IT SHALL BE THE RESPONSIBILITY OF THE OWNER, AGENT, |
| | PROPIETOR OR OCCUPANT OF GROUP S AND GROUP F |
| | OCCUPANCIES, OR ANY OCCUPANCY WHERE EXCESSIVE FLOOR |
| | LOADING IS LIKELY TO OCCUR, TO EMPLOY A COMPETENT |
| | ARCHITECT OR ENGINEER IN COMPUTING THE SAFE FLOOR LOAD |
| | CAPACITY. ALL SUCH COMPUTATIONS SHALL BE ACCOMPANIED BY |
| | AN AFFADAVIT FROM THE ARCHITECT OR ENGINEER STATING THE |
| | SAFE ALLOWABLE FLOOR LOADS ON EACH FLOOR IN POUNDS PER |
| | SQ FT.THE |
| | COMPUTATIONS & AFFADAVIT SHALL BE FILED AS A PERMANENT |
| | RECORD OF THE BLDG DEPT. |
| | |
| | 6C) 110.4.3.SIGNS REQUIRED. IN EVERY BUILDING OR PART |
| | OF A BUILDING USED FOR STORAGE, INDUSTRIAL OR HAZARDOUS |
| | PURPOSES, THE SAFE FLOOR LOADS, AS REVIEWED BY THE |
| | BUILDING OFFICIAL ON THE PLAN, SHALL BE MARKED ON |
| | PLATES OF APPROVED DE SIGN WHICH SHALL BE SUPPLIED & |
| | SECURELY AFFIXED BY THE OWNER OF THE BUILDING IN A |
| | CONSPICUOUS PLACE IN EACH STORY TO WHICH THEY RELATE. |
| | SUCH PLATES SHALL NOT BE REMOVED OR DEFACED, & IF LOST, |
| | REMOVED THE OWNER OF THE BUILDING SHALL REPLACE THEM. |
| | |
| | 6D) THE MEZZANINE ABOVE TTHE SHIPPING ROOM PLEASE |
| | PROVIDE DOCUMENTATION ON HOW THE AREA LIMITATION IN |
| | 505.2 IS BEING MET EVEN WITH EXCEPTION # 2. |
| | 505.2 AREA LIMITATION. THE AGGREGATE AREA OF A |
| | MEZZANINE OR MEZZANINES WITHIN A ROOM SHALL NOT EXCEED |
| | ONE-THIRD OF THE FLOOR AREA OF THAT ROOM OR SPACE IN |
| | WHICH THEY ARE LOCATED. THE ENCLOSED PORTION OF A ROOM |
| | SHALL NOT BE INCLUDED IN A DETERMINATION OF THE FLOOR |
| | AREA OF THE ROOM IN WHICH THE MEZZANINE IS LOCATED. IN |
| | DETERMINING THE ALLOWABLE MEZZANINE AREA, THE AREA OF |
| | THE MEZZANINE SHALL NOT BE INCLUDED IN THE FLOOR AREA |
| | OF THE ROOM. |
| | 2. THE AGGREGATE AREA OF MEZZANINES IN BUILDINGS AND |
| | STRUCTURES OF TYPE I OR II CONSTRUCTION SHALL NOT |
| | EXCEED ONE-HALF OF THE FLOOR AREA OF THE ROOM IN |
| | BUILDINGS AND STRUCTURES EQUIPPED THROUGHOUT WITH AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 AND AN APPROVED EMERGENCY VOICE/ALARM |
| | COMMUNICATION SYSTEM IN ACCORDANCE WITH SECTION |
| | 907.2.12.2. |
| | |
| | 7) DEPENDING ON THE OUTCOME OF OCCUPANCY TYPE, THE |
| | BUSINESS OCCUPANCY CAN NOT HAVE EXIT SIGNS TAKING THEM |
| | INTO A MORE DANGEROUS OCCUPANCY PER 1014.2.NOTE |
| | BUSINESS TO F1, F2 OR H IS MORE HAZARDOUS. |
| | |
| | 8) SHEET A-3 ACCESSIBILITY: 202.4. DISPROPORTIONATE |
| | COST, PLEASE SEE DOOR TO OFFICE 106 DOES NOT HAVE THE |
| | REQUIRED 18" ON THE LATCH SIDE OF THE DOOR404.2.4. |
| | |
| | 9) GANGED BATHROOMS WITH AN ACCESSIBLE STALL NEAR ROOM |
| | 103 & 114 DO NOT HAVE DOORS SHOWN ON THE STALLS, DOORS |
| | CAN NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR |
| | FIXTURES 604.8.2.2. |
| | |
| | 10) GRAB BARS FOR RESTROOMS ARE NOW MEASURED FROM THE |
| | TOP OF THE BAR NOT THE CENTER, RANGE BETWEEN 33 -36 |
| | INCHES TO TOP OF BAR. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |