| Plan Review Notes For Permit 12050324 |
| Permit Number |
12050324 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-10 16:55:33 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC | | | | | | 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED: ENGINEER | | | TO REVISE BUILDING EXPOSURE. ACCORDING TO SEC. | | | R301.2.1.4.3 THIS BUILDING IS LOCATED ON EXPOSURE "D" | | | NOT "C". REVISE BUILDING EXPOSURE, DESIGN PRESSURES AND | | | ENHANCED FASTENING ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|