Date Text
2012-05-30 16:12:102010 FBC
  
 DENIED BY PLUMBING
  
 1) THE FIXTURES THAT ARE TIED INTO THE 3" VERTICAL
 STACK ARE NOT PROPERLY VENTED. PER FBCR P3108.2.1 NOT
 MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN. THERE SHOULD
 BE A VENT BETWEEN THE W.C. AND THE SHOWER OR THE SHOWER
 CAN TIE DIRECTLY INTO THE VERTICAL VENT ABOVE THE WATER
 CLOSETS.
  