| Plan Review Notes For Permit 12050298 |
| Permit Number |
12050298 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-30 17:11:46 | 12050298 | | | 245 MURRAY ROAD | | | ADDITION/ RENOVATION | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314 | | | VERIFY WORKING CLEARANCES FOR AC #1 TO THE ELECTRIC | | | DISCONNECT AND ACCESS PANELS. NEC 110.26 | | | THE NEW BATHROOMS REQUIRE A 20 AMP BRANCH CIRCUIT FOR | | | RECEPTACLES OUTLETS. NEC 210.11 (C) (3) | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | | | | | | | | | | |
|