2012-05-31 11:23:112010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND LOAD DATA ON SHEET A-1.1 IS NOT CORRECT FOR
 THE 2010 FBC. THE WIND SPEED FOR THIS PROJECT IS 170
 MPH EXPOSURE C. THE CODE NOW REFERENCES ASCE 7-10 NOT
 05. THE CODE NOW REFERENCES ACI-08 NOT THE 2005
 EDITION. PLEASE REVISE. SEE FBC R301.2.1.1 AND CHAPTER
 43
  
 2) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS IN ALL ROOF ZONES
 REGARDLESS OF THE HEIGHT OF THE STRUCTURE. PLEASE
 REVISE THE NAILING SCHEDULE ON SHEET A-1.1 .
  
 3) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063
 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED AT THE
 BOTTOM OF ALL FRAMED EXTERIOR STUCCO WALLS BELOW THE
 FLOOR LINE WHERE THE WALL IS SUPPORTED BY A FLOOR OR
 FOUNDATION.
  
 4) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE
 EXTERIOR STUCCO.
  
 5) SHOW THAT THE UNDER-FLOOR SPACE VENTILATION REQUIRED
 BY FBC R408.1 FOR THE EXISTING CRAWL SPACE WILL NOT BE
 COMPROMISED BY THE ADDITION'S MONOLITHIC FOUNDATION.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD FOR THE NEW EXTERIOR WINDOWS, BARREL TILE
 ROOFING AND MODIFIED ROOFING FOR THE FLAT ROOF AS
 REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENTS
 107.3.4.1.
  