| 2012-05-31 11:23:11 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE WIND LOAD DATA ON SHEET A-1.1 IS NOT CORRECT FOR | | | THE 2010 FBC. THE WIND SPEED FOR THIS PROJECT IS 170 | | | MPH EXPOSURE C. THE CODE NOW REFERENCES ASCE 7-10 NOT | | | 05. THE CODE NOW REFERENCES ACI-08 NOT THE 2005 | | | EDITION. PLEASE REVISE. SEE FBC R301.2.1.1 AND CHAPTER | | | 43 | | | | | | 2) FBC R803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE | | | FASTENED WITH 8D RING SHANK NAILS IN ALL ROOF ZONES | | | REGARDLESS OF THE HEIGHT OF THE STRUCTURE. PLEASE | | | REVISE THE NAILING SCHEDULE ON SHEET A-1.1 . | | | | | | 3) SHOW COMPLIANCE WITH FBC R703.6.2 AND ASTM C 1063 | | | 7.11.5 WHICH REQUIRES A FOUNDATION WEEP SCREED AT THE | | | BOTTOM OF ALL FRAMED EXTERIOR STUCCO WALLS BELOW THE | | | FLOOR LINE WHERE THE WALL IS SUPPORTED BY A FLOOR OR | | | FOUNDATION. | | | | | | 4) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A | | | BOND BREAK BETWEEN THE WATER-RESISTIVE BARRIER AND THE | | | EXTERIOR STUCCO. | | | | | | 5) SHOW THAT THE UNDER-FLOOR SPACE VENTILATION REQUIRED | | | BY FBC R408.1 FOR THE EXISTING CRAWL SPACE WILL NOT BE | | | COMPROMISED BY THE ADDITION'S MONOLITHIC FOUNDATION. | | | | | | 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD FOR THE NEW EXTERIOR WINDOWS, BARREL TILE | | | ROOFING AND MODIFIED ROOFING FOR THE FLAT ROOF AS | | | REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENTS | | | 107.3.4.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|