| Notes |
| Date |
Text |
| 2012-09-07 15:02:48 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | | COMMENTS. | | | 2010 FBC. | | | | | | 1- PROPOSING TO USE SINGLE PEEL AND STICK SHINGLES | | | UNDERLAYMENT INSTEAD OF 2 LAYERS OF UNDERLAYMENT AS | | | REQUIRED BY SEC. R905.2.2: | | | | | | PROVIDE LETTER ADDRESSED TO THE BUILDING OFFICIAL (DOUG | | | WISE) REQUESTING APPROVAL OF THE PROPOSED APPLICATION | | | UNDER THE ALTERNATIVE MATERIALS AND METHODS SEC. 104.11 | | | OF CITY AMENDMENTS TO THE FBC 2010. | | | CLARIFY IF USING A DIRECT PEEL AND STICK APPLICATION TO | | | THE WOOD DECK. NOA 11-0601.10 SUBMITTED REQUIRES BASE | | | SHEET TO BE MECHANICALLY FASTENED. THEREFORE THIS NOA | | | CAN'T BE USED. NEED TO PROVIDE PRODUCT APPROVAL THAT | | | LISTS DIRECT DECK APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|