| 2012-05-10 09:43:27 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- PROPOSING TO USE SINGLE PEEL AND STICK SHINGLES | | | UNDERLAYMENT INSTEAD OF 2 LAYERS OF UNDERLAYMENT AS | | | REQUIRED BY SEC. R905.2.2: | | | | | | PROVIDE LETTER ADDRESSED TO THE BUILDING OFFICIAL (DOUG | | | WISE) REQUESTING APPROVAL OF THE PROPOSED APPLICATION | | | UNDER THE ALTERNATIVE MATERIALS AND METHODS SEC. 104.11 | | | OF CITY AMENDMENTS TO THE FBC 2010. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR PEEL AND | | | STICK UNDERLAYMENT DESIGNED TO BE USED FOR SHINGLES | | | APPLICATION AS REQUIRED BY DCA RULE 9N-3. NOA | | | 08-0226.06 SUBMITTED IS FOR FLAT ROOF ASSEMBLIES NO FOR | | | SHINGLES UNDERLAYMENT. | | | | | | 3- PLEASE NOTE THAT INSTALLING PEEL AND STICK | | | UNDERLAYMENT MAY VOID THE SHINGLES WARRANTY AND ROOF | | | VENTILATION ISSUES MAY NEED TO BE ADDRESSED. PLEASE | | | CONTACT SHINGLES MANUFACTURER AND PLYWOOD ASSOCIATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|