| Plan Review Notes For Permit 12050215 |
| Permit Number |
12050215 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-08 15:36:49 | BUILDING REVIEW 2ND REVIEW. | | | 2010 FBC. | | | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | 101.4.3 AND 401 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | 2-WALL SECTION ON SHEET #2: | | | A) REVISED CLOSET WALL SECTION SPECIFIES R-19 ROOF | | | INSULATION. R-19 INSULATION DOESN'T FIT ON THE 2X6 | | | RAFTERS. REVISE AS REQUIRED. COORDINATE R-VALUE WITH | | | THE ONE REQUIRED ON THE ENERGY CALCULATIONS. | | | ***NOTE: ENERGY CALCULATIONS REQUIRE R-30 MIN. FOR | | | CEILING INSULATION. SEE TABLE 402.1.1 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|