Plan Review Notes
Plan Review Notes For Permit 12050215
Permit Number 12050215
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-16 10:15:59RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE AND 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 401
 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- WALL SECTION ON SHEET #2:
 A) CLOSET WALL SECTION SPECIFIES R-30 ROOF INSULATION.
 R-30 INSULATION DOESN'T FIT ON THE 2X6 RAFTERS. REVISE
 AS REQUIRED. COORDINATE R-VALUE WITH THE ONE REQUIRED
 ON THE ENERGY CALCULATIONS.
  
 B) SPECIFY 7/8" MIN. STUCCO THICKNESS AS REQUIRED BY
 TABLE R702.1(1).
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON
 LAST PAGE OF NOA 08-0410.09 SUBMITTED. CALCULATIONS ARE
 REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1.4.3.
 NOTE: PROVIDE 2 COPIES OF RAS 117 CALCULATIONS AND ONE
 MORE COPY OF THE NOA. ONLY ONE NOA WAS SUBMITTED.
  
 B) CASEMENT WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 C) HORIZONTAL SLIDING WINDOW. PROVIDE 2 COPIES. ONLY
 ONE NOA WAS SUBMITTED.
  
 D) FIXED WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 E) SINGLE HUNG WINDOW. PROVIDE 2 COPIES. ONLY ONE NOA
 WAS SUBMITTED.
  
 F) WINDOW MULLIONS. PROVIDE 2 COPIES. ONLY ONE NOA WAS
 SUBMITTED.
  
 5- ENGINEER OF RECORD IS SPECIFYING 2500 PSF SOIL
 BEARING CAPACITY. SOIL TEST PROVIDED SPECIFIES 2000 PSF
 SOIL BEARING CAPACITY. ENGINEER OF RECORD TO REVIEW
 SOIL TEST REPORT AND REVISE PLANS AS REQUIRED. REVISE
 SPECIFICATIONS ON THE DESIGN STANDARDS ON SHEET 1,
 FOUNDATION NOTES ON SHEET 1 AND CLOSET WALL SECTION ON
 SHEET 2.
  
 6- SOIL TEST REPORT TO HAVE ENGINEER'S ORIGINAL SEAL
 AND SIGNATURE (NO COPIES) AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES. AND, PROVIDE 2 COPIES. ONLY ONE COPY
 WAS SUBMITTED.
  