| Plan Review Notes For Permit 12050179 |
| Permit Number |
12050179 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-29 11:01:45 | 400 NORTH FLAGLER DRIVE - PENTHOUSE C5 | | | PERMIT #12050179 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS PROVIDED ON THE PLANS (1801 S FLAGLER | | | DRIVE) DOES NOT MATCH THE ADDRESS PROVIDED ON THE | | | PERMIT APPLICATION (400 N FLAGLER DRIVE). | | | | | | SHEET 2 OF 2 ON ONE SET OF PLANS IS NOT STAMPED BY THE | | | ARCHITECT. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM. SPRINKLER | | | PROTECTION NEEDED FOR ADDED INTERIOR SPACE (PREVIOUSLY | | | EXTERIOR BALCONY). | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|