| 2012-05-14 13:36:42 | 477 SOUTH ROSEMARY AVENUE - SUITE #323 |
| | PERMIT #12050137 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | IN ADDITION TO THE FLORIDA BUILDING CODE, THE DESIGN |
| | SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE FLORIDA 2009 EDITION |
| | OF NFPA 1 AND NFPA 101. |
| | |
| | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| | OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. POST "NO SMOKING" SIGNS IN |
| | CONSTRUCTION AREA. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | THE SUITE IS FUNCTIONING AS A MIXED-USE, NON-SEPARATED |
| | OCCUPANCY. THE MIXED-USE (BUSINESS, ASSEMBLY, |
| | EDUCATION) OCCUPANCIES SHALL HAVE THE MEANS OF EGRESS, |
| | PROTECTION, AND OTHER SAFEGUARDS IN THE BUILDING THAT |
| | COMPLY WITH THE MOST RESTRICTIVE FIRE AND LIFE SAFETY |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED. NOTE: THE |
| | SUITE HAS ONLY ONE EXIT ACCESS PATH WHICH WOULD NOT BE |
| | ALLOWED FOR AN ASSEMBLY OCCUPANCY WITH MORE THAN 50 |
| | PERSONS. |
| | |
| | PROVIDE OCCUPANCY LOADS BASED UPON ACTUAL USE OF EACH |
| | SPACE AND NOT THE OVERALL BUSINESS OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY |
| | LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A |
| | LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE |
| | RELEASED FROM THE EGRESS SIDE OF THE DOOR. |
| | |
| | INDICATE THE SMOKE AND FLAME SPREAD CLASSIFICATION OF |
| | THE INTERIOR WALL AND CEILING FINISH MATERIALS. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL (NOT JUST ENTRANCE) |
| | DOORS WITH EXIT SIGNS. |
| | |
| | THE RESOURCE ROOM TRAVEL DISTANCE TO A PORTABLE FIRE |
| | EXTINGUISHER EXCEEDS 75 FEET. |
| | |
| | EACH FIRE-RATED WALL SHALL BE PERMANENTLY IDENTIFIED |
| | WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| | CENTER. |
| | |
| | IT MAY BE DIFFICULT TO MEET THE MINIMUM AUDIBILITY |
| | REQUIREMENTS OF NFPA 72 WITH ONLY TWO HORN-STROBE FIRE |
| | ALARM DEVICES. |
| | |
| | NOTE: EXISTING SUITE MAY HAVE RESIDENTIAL STYLE |
| | SPRINKLERS THAT NEED TO BE REPLACED WITH COMMERCIAL |
| | STYLE SPRINKLERS. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |
| | |