| Plan Review Notes For Permit 12050131 |
| Permit Number |
12050131 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-07 08:55:01 | 2007 FBC W/2009 REVISIONS | | | | | | REVISION DENIED BY MECHANICAL | | | | | | 1) THE REVISION THAT WAS SUBMITTED IS ON PLAN SHEET 4. | | | SHEET 4 OF THE APPROVED PLANS IS THE PROPOSED FLOOR | | | PLAN AND THE PLUMBING PLAN. THE APPROVED MECHANICAL | | | PLANS ARE ON SHEET 9. PLEASE SUBMIT THE PROPOSED | | | MECHANICAL REVISIONS ON SHEET 9. CITY AMENDMENTS | | | 106.1.2 | | | | | | 2) THE APPROVED MECHANICAL PLAN ON SHEET ARE SIGNED AND | | | SEALED BY THE ENGINEER, LUIS LOPEZ. FLORIDA STATUTE FS | | | 471 REQUIRES THE REVISED PLANS ARE REQUIRED TO BY | | | SIGNED AND SEALED BY HIM. | | | | | | 3) THE REVISED PLAN DOES NOT SHOW THE LOCATIONS OF | | | CONDENSING UNITS AND DISCONNECTS. FBC M1401 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|