| Plan Review Notes For Permit 12050036 |
| Permit Number |
12050036 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-10 13:39:55 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE WIND MAP, WEST PALM BEACH LIES BETWEEN THE LINE | | | FOR 160MPH AND 170MPH. FBC RESIDENTIAL 301.2. PLEASE | | | USE 170MPH OR IF ANOTHER WIND SPEED BETWEEN 160MPH AND | | | 170MPH IS USED, PROVIDE INFORMATION REGARDING HOW THE | | | WIND SPEED WAS DETERMINED. | | | | | | 2. 9" SPACING DOES NOT MEET MINIMUMS IN PRODUCT | | | APPROVAL FOR OPENINGS 8' AND GREATER, SEE SHEET 6, | | | CONNECTION TYPE 1. | | | | | | 3. SPANS SHOULD EQUAL BLADE LENGTH, SHOULD NOT BE THE | | | SAME AS OPENING SIZE FOR A WALL MOUNT. PLEASE REVISE | | | INSTALLATION SCHEDULE. | | | | | | 4. PLEASE INCLUDE INFORMATION REGARDING TYPE OF | | | INSTALLATION; KNUCKLE OR LOCK/CENTERMATES IN ORDER TO | | | DETERMINE SHUTTER GLASS SEPARATION REQUIRED, SEE SHEET | | | 5 OF PRODUCT APPROVAL. | | | | | | | | | |
|