| Plan Review Notes For Permit 12040736 |
| Permit Number |
12040736 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-07 09:11:30 | FBC 2010 PLUMBING | | | FBC 2010 ACCESSIBILITY | | | REVIEW #1 | | | DENIED: | | | | | | SEET A2.01 TABLE FOR SUITE 5 LISTS RESTROOMS AS UNISEX. | | | SEPARATE FACILITIES ARE REQUIRED AND SHALL MEET THE | | | REQUIREMENTS OF THE ACCESSIBILITY CODE. | | | 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE | | | REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR | | | EACH SEX. | | | | | | SHEET A2.01 FOR SUITE 1 THE RESTROOMS HAVE BEEN | | | RECONFIGURED. THE MENS ROOM WOULD NOT COMPLY WITH FBC | | | ACCESSIBILITY 603.2 TURNING SPACE AND 602.3 DOOR SWING. | | | ALSO, SEE FBC ACCESSABILITY 202.4.1 AND 202.4.2 | | | DISPROPORTIONATE COST. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|