| Plan Review Notes For Permit 12040736 |
| Permit Number |
12040736 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-02 15:05:57 | PROVIDE AN ELECTRICAL PLAN WITH AN ELECTRICAL RISER | | | PLAN SHOWING IN DETAIL THE CHANGES TO THE EXISITING | | | SYSTEM. PROVIDE A PANEL SCHEDULE FOR THE NEW AND | | | EXISTING OFFICE SPACES WITH A SUMMARY LOAD CALCULATION. | | | NEC 215.5 | | | ELECTRICAL PANELS CANNOT BE LOCATED IN CLOSETS AND | | | STORAGE ROOMS. SHOW LOCATION OF RELOCATED PANEL A-2NEC | | | 408.17 | | | ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST | | | BE GFCI PROTECTED. NEC 210.8 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|