Plan Review Notes
Plan Review Notes For Permit 12040736
Permit Number 12040736
Review Stop E
Sequence Number 1
Notes
Date Text
2012-05-02 15:05:57PROVIDE AN ELECTRICAL PLAN WITH AN ELECTRICAL RISER
 PLAN SHOWING IN DETAIL THE CHANGES TO THE EXISITING
 SYSTEM. PROVIDE A PANEL SCHEDULE FOR THE NEW AND
 EXISTING OFFICE SPACES WITH A SUMMARY LOAD CALCULATION.
 NEC 215.5
 ELECTRICAL PANELS CANNOT BE LOCATED IN CLOSETS AND
 STORAGE ROOMS. SHOW LOCATION OF RELOCATED PANEL A-2NEC
 408.17
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  