| Plan Review Notes For Permit 12040733 |
| Permit Number |
12040733 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-03 15:28:58 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED, | | | FAC9N-3. INSTALLATION INSTRUCTIONS WERE PROVIDED BUT | | | THEY APPEAR TO BE FOR FBC2007. | | | | | | PROVIDE EVALUATION REPORT, INSTALLATION INSTRUCTIONS, | | | AND FLORIDA STATE PRODUCT APPROVAL COVER SHEET (OR | | | MIAMI DADE NOA). REVISE INSTALLATION SCHEDULE | | | ACCORDINGLY. | | | | | | 2. PLEASE NOTE THAT DESIGN PRESSURES ARE VERY HIGH. | | | PLEASE BE ADVISED THAT "WORST CASE" (25' HIGH, EXPOSURE | | | C, 170MPH, WALL ZONE 5, 10SF) ACCORDING TO FBC | | | RESIDENTIAL IS +42.3 / -56.6. ZONE 4 PRESSURES FOR SAME | | | CONDITIONS ARE 42.3 / -45.8. | | | | | | CONTRACTOR MAY ELECT TO EXCEED MINIMUM CODE COMPLIANCE. | | | HOWEVER, NOTE THAT THE ANCHOR SPACING PROPOSED DOES NOT | | | COMPLY WITH THE DESIGN PRESSURE OF -94.4 (FROM | | | INSTALLATION SCHEDULE). PLEASE FEEL FREE TO CONTACT ME | | | IF YOU NEED ASSISTANCE. | | | | | | | | | | | | |
|