Plan Review Notes
Plan Review Notes For Permit 12040733
Permit Number 12040733
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-03 15:28:58****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3. INSTALLATION INSTRUCTIONS WERE PROVIDED BUT
 THEY APPEAR TO BE FOR FBC2007.
  
 PROVIDE EVALUATION REPORT, INSTALLATION INSTRUCTIONS,
 AND FLORIDA STATE PRODUCT APPROVAL COVER SHEET (OR
 MIAMI DADE NOA). REVISE INSTALLATION SCHEDULE
 ACCORDINGLY.
  
 2. PLEASE NOTE THAT DESIGN PRESSURES ARE VERY HIGH.
 PLEASE BE ADVISED THAT "WORST CASE" (25' HIGH, EXPOSURE
 C, 170MPH, WALL ZONE 5, 10SF) ACCORDING TO FBC
 RESIDENTIAL IS +42.3 / -56.6. ZONE 4 PRESSURES FOR SAME
 CONDITIONS ARE 42.3 / -45.8.
  
 CONTRACTOR MAY ELECT TO EXCEED MINIMUM CODE COMPLIANCE.
 HOWEVER, NOTE THAT THE ANCHOR SPACING PROPOSED DOES NOT
 COMPLY WITH THE DESIGN PRESSURE OF -94.4 (FROM
 INSTALLATION SCHEDULE). PLEASE FEEL FREE TO CONTACT ME
 IF YOU NEED ASSISTANCE.
  
  
  
  