| Plan Review Notes For Permit 12040652 |
| Permit Number |
12040652 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-04 15:03:27 | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | PLEASE SEE BUILDING REVIEW NOTES BELOW: | | | | | | 1) SHEET 1 PLEASE SEE NEW 2010 ACCESSIBILITY CODE AND | | | FIGURE 604.8.1.6 WHEELCHAIR ACCESSIBLE TOILET | | | COMPARTMENT IN NEW CONSTRUCTION. THE MINIMUM DIMENSIONS | | | ARE 84 1/2 " X 60" WITH THE WATERCLOSET AND LAV LOCATED | | | ON THE 84 1/2" WALL. THE LAV CAN NOT OVER LAP INTO THE | | | CLEAR FLOOR SPACE FOR THE WATER CLOSET.SEE FIGURE | | | 604.3.1. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|