| 2012-09-14 16:12:47 | BUILDING PLAN REVIEW |
| | PERMIT: 12040588 |
| | ADD:2700 BROADWAY |
| | CONT: PKS CONSTRUCTION |
| | TEL: (561)704-2394 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 3RD REVIEW |
| | SEPT. 14/2012 |
| | ENGINEER JOHN HOLT PE # 15252 |
| | |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: |
| | 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 8/29/12, |
| | PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012 |
| | IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B, |
| | PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW |
| | ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN |
| | ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010 |
| | EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND |
| | CHAPTER 11 FOR HISTORIC BUILDINGS. |
| | |
| | |
| | 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE |
| | ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE |
| | FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND |
| | TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1* |
| | MINIMUM COMMERCIAL PLAN REVIEW CRITERIA. |
| | THE PROPERTY APPRAISERS OFFICE AND CITY LIST THIS |
| | BUILDING AS A RESTROOM (I-1). PLANS INDICATE THIS AS A |
| | A-2 OCCUPANCY? |
| | SHEET A1 ALSO INDICATES THE MINIMUM BLDG TYPE AS A TYPE |
| | 5 CLASS 1 THIS IS NOT TERMINOLOGY FOUND IN TABLE 503 |
| | EITHER VA OR VB. |
| | |
| | 1C) SHEET A-1 INDICATES THE PLANS ARE DESIGNED TO THE |
| | 2010 FBC FOR WIND DESIGN BUT STILL REFERENECES ASCE |
| | 7-05 AND A IMPORTANCE FACTOR OF 1.15 WHAT IS REQUIRING |
| | THE IMPORTANCE FACTOR OF 1.15, THE 2010 WIND TABLE HAVE |
| | THIS DESIGNED INTO WHICH WIND SPEED MAP THAT IS USED, |
| | THE 170 MPH WIND ZONE MAP WILL BE A BUILDING CATEGORY |
| | OF II, THE THE EXPOSURE ZONE AND HEIGHT FACTOR ARE NOT |
| | PROVIDED WITHIN THE WIND DESIGN CRITERIA 2010 FBC-B T |
| | 1609.7.(2). PLEASE SHOW PRESSURES IN VULT. |
| | OLD COMMENT: WIND DESIGN CRITERIA IS FOR THE 2007 FBC |
| | NOT THE 2010 FBC-B PLEASE REVIEW 1609.1.1. |
| | |
| | 2-3) COMPLIED. |
| | |
| | NEW COMMENTS: |
| | |
| | 4) PRODUCT APPROVALS SUBMITTED POLYGLASS NOA |
| | 11-0425.07, & GAF MODIFIED NOA 11-0425.07 ARE STAMPED |
| | REVIEWED BY LUIS LOPEZ NOT REVIEWED BY PE JOHN HOLT, |
| | NEITHER HAS THE PRODUCT APPROVAL SANTAFE TILE, MISSION |
| | BARREL ROOFING TILE NOA 07-0626.04. |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |