| 2012-07-24 11:34:56 | BUILDING PLAN REVIEW |
| | PERMIT: 12040588 |
| | ADD:2700 BROADWAY |
| | CONT: PKS CONSTRUCTION |
| | TEL: (561)704-2394 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2ND REVIEW |
| | |
| | ENGINEER LUIS LOPEZ PE # 59805 VOLUNTARY RELINGUISHMENT |
| | 4/27/2012. JW |
| | |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1: |
| | 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 4/19/2012, |
| | PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012 |
| | IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B, |
| | PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW |
| | ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN |
| | ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010 |
| | EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND |
| | CHAPTER 11 FOR HISTORIC BUILDINGS. |
| | |
| | 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE |
| | ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE |
| | FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND |
| | TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1* |
| | MINIMUM COMMERCIAL PLAN REVIEW CRITERIA. |
| | |
| | 1C) WIND DESIGN CRITERIA IS FOR THE 2007 FBC NOT THE |
| | 2010 FBC-B PLEASE REVIEW 1609.1.1. |
| | |
| | 2) FRONT PORCH ADDITION; |
| | 2A) SHEET A2 ROOF FRAMING PLAN FAILS TO IDENTIFY BOTH |
| | B-1 CARRYING BEAM ATTACHMENTS TO THE EXISTING |
| | STRUCTURE, PART OF THE MWFRS (MAIN WIND FORCE RESITING |
| | SYSTEM) PLEASE PROVIDE TYPE OF BUCKET AND ATTACHMENT. |
| | 106.1.2* ADTIONAL INFORMATION REQUIRED / |
| | 106.3.5.1.1.(8)*. |
| | |
| | 2B) SHEET A1 FRONT PORCH DETAIL INDICATES THE ROOF |
| | JOIST ANCHORING TO BEAM B1 BUT THIS DETAIL NOR THE |
| | DETAIL ON A2 PROVIDE THE CANTILVERED ROOF JOIST |
| | ATTACHMENT TO BEAM B-1 NOR THE COMMON JOIST THEY ATTACH |
| | TOO? PART OF THE MWFRS, 106.3.5.1.1(8)*. |
| | |
| | 2C) THE SAME DETAIL INDICATES THE ATTACHMENT OF LEDGER |
| | TO THE WALL WITH 1/2" BOLTS @ 4'-0" O.C.? PLANS LACK |
| | THE TYPE OF ANCHOR TO BE INSTALLED, LENGTH OF ANCHOR, |
| | IS THIS ANCHOR GOING TO BE INSTALLED INTO A CONCRETE |
| | BEAM, FILLED MASONRY BLOCK BEAM OR EMPTY CONCRETE BLOCK |
| | UNITS. |
| | |
| | 2D) SHEET A-1 FRONT PORCH DETAIL INDICATES THE ROOFING |
| | MATERIALS TO BE MODIFIED PEEL AND STICK ROOFING WHERE |
| | AS THE ACTUAL PRODUCT APPROVAL IS A GAF RUBEROID |
| | MODIFIED BITUMEN ROOF SYSTEM FOR ROOF DECKS WHICH IS |
| | CORRECT? IF THE PEEL AND STICK NOTE IS DELETED AND THIS |
| | APPROVAL WILL BE INSTALLED THEN PLEASE IDENTIFY WHICH |
| | OF THE SUB-SYSTEMS WILL BE APPLIED, PLEASE NOTE THAT IN |
| | ROOF ZONES 2 & 3 ENHANCED FASTENING WILL BE REQUIRED |
| | WHEN LIMITATION NOTE # 7 APPEARS LIMITATION NOTE # 9 |
| | DOES NOT ALLOW FOR ENHANCED FASTENING. |
| | |
| | 3) BACK PORCH ADDITION, ALL OF THE CONDITIONS LISTED |
| | ABOVE ARE THE SAME CONDITIONS FOR THE BACK PORCH |
| | ADDITION. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |