2012-05-21 10:49:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS REVIEW, SAME INSTALLATION
 SCHEDULE SUBMITTED:
  
 1. FOR THE PANELS, PLEASE PROVIDE A DETAIL WHCIH SHOWS
 HOW A 7.73" SHUTTER TO GLASS SEPARATION WILL BE
 MAINTAINED IN A BLOCK OR CONCRETE WALL.
  
 NOT ADDRESSED, STILL SHOWS DIRECT MOUNT WITH 7.73"
 SEPARATION.
  
 2. FOR THE ACCORDIONS, THE SHUTTER TO GLASS SEPARATION
 CIRCLED ON SHEET 1 AND SPECIFIED ON THE INSTALLATION
 SCHEDULE IS FOR INSTALLATIONS OVER 30'. PLEASE REVISE.
  
 2ND REVIEW, UNDER 30' COLUMN CIRCLED, BUT INFORMATION
 NOT REVISED.
  
  
  