| 2012-04-24 11:17:43 | 3308 45TH STREET - #100B |
| | PERMIT #12040574 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | INDICATE THE REASON FOR INSTALLING A FIRE RATED BARRIER |
| | TO DIVIDE THE WAREHOUSE SPACE. |
| | |
| | EACH NEW SMOKE OR FIRE-RATED WALL/BARRIER SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE |
| | DETAILS FOR FIRE SEALANT AND FOR PROTECTING |
| | THROUGH-PENETRATIONS. |
| | |
| | THE TWO NEW DOORS INSTALLED ON SHEET 2 DO NOT HAVE EXIT |
| | SIGNS OR EMERGENCY LIGHTS. ARE THESE INTENDED TO BE |
| | USED AS EXIT DOORS? |
| | |
| | ONE OF THE NEW DOORS CREATES AN UNPROTECTED OPENING |
| | WITHIN 10 FEET OF THE ADJACENT BUILDING. CONFIRM THIS |
| | DOOR DOES NOT NEED TO HAVE A FIRE RESISTANCE RATING AND |
| | DOOR CLOSER. |
| | |
| | PROVIDE HANDRAIL DETAILS AS HANDRAILS ARE REQUIRED ON |
| | BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED NOT |
| | LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES ABOVE |
| | THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO THE |
| | TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD. |
| | HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR |
| | SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION |
| | SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND |
| | NOT MORE THAN 2 INCHES. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |