| Plan Review Notes For Permit 12040574 |
| Permit Number |
12040574 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-07 11:42:23 | 12040574 | | | 3308 45TH ST. #100B | | | INTERIOR RENOVATION | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY | | | THE ELECTRICAL RISER PLAN TO SHOW ALL METERS, | | | GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE | | | WHOLE BUILDING. | | | NEC 230.2, 230.71, 230.72 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|