| 2012-04-25 14:58:46 | 1015 GREEN PINE BOULEVARD |
| | PERMIT #12040571 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NO PRODUCT DATA SUBMITTED FOR MANUAL PULL STATIONS. ADD |
| | PULL STATIONS TO SCOPE OF WORK AND TOTAL JOB VALUE. |
| | |
| | THE QUANTITY OF DEVICES INDICATED ON THE PERMIT |
| | APPLICATION DOES NOT MATCH THE DEVICES SHOWN ON THE |
| | PLANS. |
| | |
| | THE FACP IS NOT INDICATED AS WEATHERPROOF. INDICATE THE |
| | ENCLOSURE (NEMA) RATING FOR THE FIRE ALARM CONTROL |
| | PANEL. |
| | |
| | THE RISER DIAGRAM SHOWS TWO TELEPHONE LINES. INDICATE |
| | IF THE FIRE ALARM SYSTEM IS MONITORED OR ONLY INSTALLED |
| | FOR LOCAL ALARM. |
| | |
| | FIRE ALARM PLANS WITH A JOB VALUE GREATER THAN $5,000 |
| | ARE REQUIRED TO BE SIGNED/SEALED BY A PROFESSIONAL |
| | ENGINEER. |
| | |
| | INDICATE THE SOUND PRESSURE LEVEL (DB) TO BE PROVIDED |
| | AT THE PILLOW IN SLEEPING AREAS. |
| | |
| | NOTE:PER FLORIDA ADMINISTRATIVE CODE 69A-48.002, THESE |
| | RULES APPLY TO BOTH NEW AND EXISTING FIRE ALARM SYSTEMS |
| | AS OF THE EFFECTIVE DATE OF THE RULE. THOSE SYSTEMS |
| | WHICH WERE BASED ON PRODUCT AND ENGINEERING PRACTICES |
| | RECOGNIZED AS BEING ACCEPTABLE AT THE DATE OF |
| | INSTALLATION BUT ARE NOT IN COMPLIANCE WITH CURRENTLY |
| | ADOPTED STANDARDS MAY CONTINUE IN USE, PROVIDED THEY |
| | ARE FUNCTIONAL AND APPROVED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |