| Plan Review Notes For Permit 12040563 |
| Permit Number |
12040563 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-25 14:38:43 | 1010 GREEN PINE BOULEVARD | | | PERMIT #12040563 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NO PRODUCT DATA SUBMITTED FOR MANUAL PULL STATIONS. ADD | | | PULL STATIONS TO SCOPE OF WORK AND TOTAL JOB VALUE. | | | NOTE: FIRE ALARM PLANS WITH A JOB VALUE GREATER THAN | | | $5,000 ARE REQUIRED TO BE SIGNED/SEALED BY A | | | PROFESSIONAL ENGINEER. | | | | | | THE FACP IS NOT INDICATED AS WEATHERPROOF. INDICATE THE | | | ENCLOSURE (NEMA) RATING FOR THE FIRE ALARM CONTROL | | | PANEL. | | | | | | THE RISER DIAGRAM SHOWS TWO TELEPHONE LINES. INDICATE | | | IF THE FIRE ALARM SYSTEM IS MONITORED OR ONLY INSTALLED | | | FOR LOCAL ALARM. | | | | | | INDICATE THE SOUND PRESSURE LEVEL (DB) TO BE PROVIDED | | | AT THE PILLOW IN SLEEPING AREAS. | | | | | | NOTE:PER FLORIDA ADMINISTRATIVE CODE 69A-48.002, THESE | | | RULES APPLY TO BOTH NEW AND EXISTING FIRE ALARM SYSTEMS | | | AS OF THE EFFECTIVE DATE OF THE RULE. THOSE SYSTEMS | | | WHICH WERE BASED ON PRODUCT AND ENGINEERING PRACTICES | | | RECOGNIZED AS BEING ACCEPTABLE AT THE DATE OF | | | INSTALLATION BUT ARE NOT IN COMPLIANCE WITH CURRENTLY | | | ADOPTED STANDARDS MAY CONTINUE IN USE, PROVIDED THEY | | | ARE FUNCTIONAL AND APPROVED BY THE AUTHORITY HAVING | | | JURISDICTION. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | | | | | | | | | | | | | | | | |
|