| Notes |
| Date |
Text |
| 2012-04-27 16:18:44 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. WEST PALM BEACH IS IN ASTM E 1996 WIND ZONE 4, FBC | | | RESIDENTIAL 301.2.1.2.1. SEE SHEET 1, ITEM 1, GENERAL | | | NOTES, THIS PRODUCT HAS BEEN TESTED FOR USE IN ZONES 1 | | | THROUGH 3 ONLY (EASTERN METAL SUPPLY PANELS, FL 11964). | | | | | | 2. FOR THE STORM PANELS, SEE SHEET 10. NOTE THAT A .35 | | | FACTOR IS TO BE APPLIED TO ANCHOR SPACING WHEN THE EDGE | | | DISTANCE IS LESS THAN 3.5". | | | | | | 3. SEE SHEET 5 OF THE ACCORDION PRODUCT APPROVAL. | | | PLEASE SPECIFY WHICH INSTALLATION IS PROPOSED; | | | "KNUCKLE" OR "LOCK/CENTERMATE" AND REVISE SHUTTER TO | | | GLASS SEPARATION ON THE INSTALLATION SCHEDULE. | | | | | | 4. SPANS SHOULD EQUAL BLADE LENGTH FOR ACCORDIONS, | | | ANCHOR TO ANCHOR FOR PANELS. PLEASE REVISE AS | | | NECESSARY. UNLESS THE INSTALLATION IS A TRAPPED MOUNT, | | | |
|