Plan Review Notes
Plan Review Notes For Permit 12040534
Permit Number 12040534
Review Stop E
Sequence Number 1
Notes
Date Text
2012-05-02 12:35:0712040534
 434 32ND STREET
 SFD REMODEL
  
 LOCATE THE ELECTRIC SERVICE, AC DISCONNECTS AND PANEL
 BOARDS ON THE PLAN. NEC 215.5
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 INDICATE THAT ALL NEW GENERAL PURPOSE BRANCH CIRCUITS
 MUST BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS.
 2008 NEC 210.12
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 RECEPTACLES IN BATHROOMS MUST BE GFCI PROTECTED. NEC
 210.8
 A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT
 AND BACK. NEC 210.70
 RELOCATED SPA REQUIRES ELECTRICAL BONDING AND GROUND
 FAULT PROTECTION. NEC 680.42, 680.42
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
  
  