| 2012-05-02 12:35:07 | 12040534 | | | 434 32ND STREET | | | SFD REMODEL | | | | | | LOCATE THE ELECTRIC SERVICE, AC DISCONNECTS AND PANEL | | | BOARDS ON THE PLAN. NEC 215.5 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | INDICATE THAT ALL NEW GENERAL PURPOSE BRANCH CIRCUITS | | | MUST BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. | | | 2008 NEC 210.12 | | | THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | RECEPTACLES IN BATHROOMS MUST BE GFCI PROTECTED. NEC | | | 210.8 | | | A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT | | | AND BACK. NEC 210.70 | | | RELOCATED SPA REQUIRES ELECTRICAL BONDING AND GROUND | | | FAULT PROTECTION. NEC 680.42, 680.42 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. 2010 FBC R314 | | | | | | ROBERT LECKY, CBO | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | | | | |
|