Plan Review Notes
Plan Review Notes For Permit 12040534
Permit Number 12040534
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-15 18:02:44RESIDENTIAL (R3) RENOVATION/ALTERATION BUILDING REVIEW
 COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE AND 2010 FBC.
  
 1- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 SCOPE OF WORK SHOWN ON PLANS IS A LOT MORE THAN THE
 SCOPE OF WORK DESCRIBED ON THE PERMIT APPLICATION.
 VALUE NEED TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN
 PROFESSIONAL FEES. PLEASE UPDATE THE VALUE TO INCLUDE
 ALL WORK SHOWN ON THE PLANS SUBMITTED (EXCEPT FOR THE
 DRIVEWAY, WHICH IS A SEPARATE PERMIT) AS REQUIRED BY
 SEC. 109.3 OF CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FRENCH DOORS. SUBMIT 2 COPIES. ONLY ONE FLORIDA
 PRODUCT APPROVAL FL14569-R2 WAS SUBMITTED.
  
 B) SINGLE HUNG WINDOWS. NOA 07-0717.05 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA. AND, PROVIDE 2 COPIES.
  
 C) GARAGE DOOR AS SHOWN ON PLANS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER ON PLANS AND DETAILS. PROVIDE ONLY THE COVER
 PAGE AND PAGE SHOWING THE CONNECTOR. THIS APPLIES TO
 THE STRUCTURAL CONNECTORS ONLY.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- SPECIFY THE DESIGN PRESSURES FOR THE NEW GARAGE
 DOOR. SEC. R301.2.1.4.3.
  
 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW TRELLIS AND WOOD DECKS
 SHOWN ON PLANS. SPECIFY WOOD FRAMING MEMBERS SIZES AND
 CONNECTORS. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 6- PLANS NEED TO PROVIDE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 7- DETAIL 5 ON SHEET S-2: SPECIFY HOW THE EXISTING
 CEILING RAFTERS ARE REINFORCED WHEN CUT TO RECEIVED THE
 NEW (3)2X8 GIRDER. ARE THESE CEILING RAFTERS OR WOOD
 TRUSSES?. AND HOW ARE THEY ATTACHED TO THE NEW GIRDER.
 SEC. 107.2.1.3 CITY AMENDMENTS TO FBC.
  
 8- THIS IA AN ALTERATION LEVEL 3 NOT 2. SEC. 405 OF
 2010 FBC-EXISTING BUILDING. REVISE INFORMATION ON
 SHEETS SP AND D1 AS REQUIRED.
  
 9- SHEET S-2: REVISE CORNER DISTANCE A ON THE WIND LOAD
 SCHEDULE. NOTE ON FIGURE R301.2(7) REQUIRES A=4 FEET IN
 ALL CASES.
  
 IF YOU HAVE ANY QUESTION, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712.