| Plan Review Notes For Permit 12040525 |
| Permit Number |
12040525 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-15 11:24:08 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) ALL PERMIT APPLICATIONS THAT WERE APPLIED FOR ON OR | | | AFTER MARCH 15, 2012 ARE REQUIRED TO COMPLY WITH THE | | | 2010 FLORIDA BUILDING CODE PER FS 553.73. THE PLANS | | | THAT WERE SUBMITTED REFERENCE THE 2007 FBC. PLEASE | | | CORRECT. | | | | | | 2) THE WINDLOAD PRESSURES SHOWN FOR THE OPENINGS AND IN | | | THE COMPONENT AND CLADDING CHART ON SHEET 1 ARE TOO LOW | | | FOR EXPOSURE CATEGORY C. PLEASE CORRECT. FBC R301.2.1 | | | | | | 3) THE ENERGY CALCULATIONS THAT WERE SUBMITTED ARE FOR | | | THE 2007 FBC ENERGY CODE. PLEASE SUBMIT THE REQUIRED | | | FORMS TO SHOW COMPLIANCE WITH THE 2010 FBC ENERGY | | | CONSERVATION SECTION 401.2. | | | | | | 4) SUBMIT CURRENT PRODUCT APPROVALS THAT COMPLY WITH | | | THE 2010 CODE AS REQUIRED BY DCA RULE 9N-3. THE PRODUCT | | | APPROVAL FOR NOA NO. 07-0828.06 (TRACO MULLIONS) HAS | | | EXPIRED. | | | | | | 5) SUBMIT TWO COPIES OF A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS THAT WILL BE INSTALLED. | | | AN INSTALLATION SCHEDULE IS AVAILABLE ON THE | | | CONSTRUCTION SERVICES WEBSITE HTTP://WWW.CITYOFWPB.COM/ | | | CONSTRUCTION/PERMITS_PERMIT_INFORMATION.PHP | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|