| Plan Review Notes For Permit 12040512 |
| Permit Number |
12040512 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-05-16 07:40:11 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THE SITE SPECIFIC FOR PROPOSED CONSTRUCTION WAS NOT | | | PROVIDED. THE SHEETS PROVIDED ARE FROM TWO DIFFERENT | | | CHAPTERS, SCREEN ROOM AND SCREEN ENCLOSURES. ISN'T THE | | | PROPOSED CONSTRUCTION UNDER AN EXISTING ROOF AND OVER | | | AN EXISTING SLAB? PROVIDE DETAILS FROM THE APPROPRIATE | | | SECTION OF THE AAF GUIDE, INCLUDE SPAN CHARTS, ALL | | | APPLICABLE DETAILS. | | | | | | NOTE - PREVIOUS SUBMITTAL COMMENTS WERE GIVEN TO | | | CONTRACTOR VERBALLY, INCORRECT WIND SPEED AND EXPOSURE | | | SUBMITTED, PLANS TO BE MINIMUM OF 140MPH V(ASD) | | | EXPOSURE C. | | | | | | | | | | | | |
|